Vatteninstallationer

Kommittébeteckning: SIS/TK 198 (Vatten- och avloppssystem)
Källa: CEN
Svarsdatum: den 10 jun 2019
Se merSe mindre
 

This document specifies:

a) the field of application;

b) the requirements of hose union anti vacuum valves;

c) dimensional and physio-chemical properties, and properties of general hydraulic, mechanical and acoustic design of hose union anti-vacuum valves of nominal sizes DN 15 up to and including DN 25;

d) marking and technical product information.

This document specifies the characteristics of hose union anti-vacuum valves of nominal size DN 15 up to and including DN 25 that are suitable for use in drinking water systems at pressures up to and including 1 MPa (10 bar) and temperatures up to and including 65 °C and for 1 h at 90 °C.

HB protects against back siphonage only and is installed in vertical downward flow position.

HB and HD anti-vacuum valves are for installation exclusively at the connecting point between stop valve and hose in vertical downward flow position.